Stream from a PLC over Modbus

Read a PLC, power meter or controller over Modbus TCP or RTU. Each register you map becomes a channel.

Before you start

  • For TCP, the device's address and port (usually 502). For RTU, its serial port (/dev/ttyUSB0, COM3) and line settings.
  • Its unit ID — usually 1.
  • Its register map, from the device manual.

Steps

  1. Open Connectors, search for modbus, and press Install.

  2. Open Inputs, press Add input, and choose modbus.

  3. Fill the fields:

    FieldExample
    Device nameplc1 — channels read /modbus/plc1/…
    Connection (host:port or serial device)192.168.1.60:502 or /dev/ttyUSB0
    Transporttcp (default) or rtu
    Unit ID1
    Poll rate (Hz)10

    For rtu, also set Serial baud rate (RTU), Serial parity (RTU), Serial stop bits (RTU) and Serial data bits (RTU). Defaults are 9600 8N1.

  4. Paste your device's map into Register map (JSON), one entry per value:

    [{"alias": "temp", "address": 0, "kind": "input", "dtype": "i16",
      "scale": {"gain": 0.1, "offset": 0}, "unit": "degC"},
     {"alias": "pump_speed_sp", "address": 10, "kind": "holding",
      "dtype": "u16", "unit": "rpm", "writable": true}]
    KeyValue
    aliasthe channel's last path segment
    addresszero-based — a manual's 40001 is 0
    kindinput · holding · coil · discrete
    dtypeu16 · i16 · u32 · i32 · f32; bool for coil and discrete
    scalegain and offset into engineering units
    writabletrue to accept setpoints
  5. Press Test connection. It reads the first mapped register. A pass means the device answered.

  6. Press Add & start.

  7. In Channels, type a name and unit for each, such as temp → bearing temperature, degC.

Check it worked

On Inputs, the row counts samples at about your poll rate. On Live, each value shows as /modbus/plc1/<alias>.

Tip

A 32-bit value reads as nonsense? Add "word_swap": true to its map entry. Some devices send the low word first.