Read and write PLCs, power meters, sensors and process controllers over Modbus TCP or serial (RTU). One connector covers any Modbus device: you describe yours with a register map. No code needed.

What you get

  • Live readings — each mapped value is its own channel, scaled into engineering units.
  • Setpoints — values marked writable can be set from Trellis via ch.write(path, value). Each write is read back, so you see what the device took.
  • One device per input, named by its Device name. Channels read /modbus/plc1/….

Setup

  1. Note the device's address and unit ID (usually 1). The standard Modbus TCP port is 502. For an RTU device, note its serial port (/dev/ttyUSB0, COM3) and line settings.
  2. In Inputs, choose Add input, pick modbus, and fill in:
    • Device name — a short label, e.g. plc1
    • Connection — 192.168.1.60:502, or the serial port for RTU
    • Transport — tcp (default) or rtu. RTU uses Serial baud rate / parity / stop bits / data bits (default 9600 8N1).
    • Model — pick a built-in map, or paste your device's map into Register map. Each entry names a value, its address, type and scaling.
  3. Press Test connection. It reads the first mapped register, so a pass means the device answered.
  4. Channels appear on Live. Writable entries are available in Trellis.
  5. In the Channels table, give a channel a name and unit, such as temp → bearing temperature, degC.

Register map example

[
  {"alias": "temp", "address": 0, "kind": "input", "dtype": "i16",
   "scale": {"gain": 0.1, "offset": 0}, "unit": "degC"},
  {"alias": "pump_speed_sp", "address": 10, "kind": "holding",
   "dtype": "u16", "unit": "rpm", "writable": true}
]
  • Addresses are zero-based: a manual's 40001 is address 0.
  • Types: u16, i16, u32, i32, f32, and bool for coils and discrete inputs.
  • For a 32-bit value sent low word first, set word_swap.

Dead-man (heartbeat)

If this computer hangs, loses power or loses the network, a Modbus output keeps its last value. A dead-man lets your PLC take over. While a test setup is deployed, Phloem keeps changing a heartbeat register. Your PLC drives its outputs safe when the heartbeat stops changing.

Your PLC needs a few lines of logic, or a drive's communication-loss setting:

  • The heartbeat is one holding register (u16).
  • 0 means "not supervised": do nothing while it reads 0.
  • Any other value must change at least once per timeout. If it does not, drive the outputs to their safe states.

Then fill in the input's Dead-man section:

  • Heartbeat register — the alias of that register in your map. Map it without writable, so a test setup can never write it.
  • PLC timeout (s) — the timeout you set in the PLC. Phloem uses it to decide how often to write.
  • Outputs the PLC drives safe — the writable aliases your PLC makes safe. Outputs you leave out show as not credited to the dead-man.
{"alias": "heartbeat", "address": 100, "kind": "holding", "dtype": "u16"}

When a setup is undeployed, Phloem writes 0. The PLC stops supervising and leaves the outputs where they are. Pick a timeout longer than your slowest write; a few seconds suits most networks.

Notes

  • A device we have never seen works as soon as you paste its map.
  • Writes are checked against the map before they are sent. Every write is recorded.

#Supports

  • Any Modbus-TCP device via a register map (paste your device's map)
  • Any Modbus-RTU (serial) device via the same register map

#Connection fields

Every field the Add input form shows for this connector.

FieldTypeRequiredDefault
Device name
plc1
TextYes—
Connection (host:port or serial device)
192.168.1.60:502 | /dev/ttyUSB0
TextYes—
Transport
tcp | rtu
Text—tcp
Serial baud rate (RTU)
9600
Number—9600
Serial parity (RTU)
none | even | odd
Text—none
Serial stop bits (RTU)
1 | 2
Number—1
Serial data bits (RTU)
8
Number—8
Unit ID
1
Number—1
Model (built-in map)
leave empty when pasting a map
Text——
Register map (JSON)
[{"alias":"temp","address":40001,...}]
Text——
Poll rate (Hz)
1
Number—1
Heartbeat register (alias)
The alias of a one-word holding register your PLC watches. Map it read-only: the connector writes it, a document never can. Empty = no dead-man.
heartbeat
Text——
PLC timeout (s)
How long your PLC waits on an unchanged heartbeat before it drives the outputs safe — the value configured in the PLC.
2
Number——
Outputs the PLC drives safe
The writable aliases your PLC drives to a safe state when the heartbeat stops.
valve, pump_speed_sp
Text——